SPECIFICATIONS
Connection Data:
Rigid Solid AWG (mm2): 26 to 14 (0.14 to 2.5)
Flexible Stranded AWG (mm2): 26 to 14 (0.14 to 2.5)
Input Voltage:
XRU1H24U: 24 Vac/Vdc
XRU1H120U: 120 Vac/110 Vdc
Typical Input Current:
XRU1H24U: 17.5 mA
XRU1H120U: 4.5 mA (120 Vac)/4.2 mA (110 Vdc)
Typical Response Time:
XRU1H24U: 8 mS
XRU1H120U: 7 mS
Typical Release Time: 10 mS
Input Protection: Bridge rectifier
OUTPUT DATA
Contact Type: Single contact, SPDT
Contact Material: AgNi
Max Switching Voltage: 250 Vac/Vdc1
Min Switching Voltage: 12 Vac/Vdc
Limiting Continuous Current: 10 A (6 A)2
Max Inrush Current: 30 A (300 mS)
Min Switching Current: 100 mA
Min Switching Power: 1.2 W
MISCELLANEOUS DATA
Test Voltage I/O: 4 kV, 50 Hz, 1 min
Ambient Temp Range: -20 to 60掳C (-4 to 140掳F)
Rated Operating Mode: *** Operating Factor
Inflammability Class: V0, in Accordance with UL 94
Mechanical Service Life: 3 x 107 cycles
1 The separating plate, XRAPLCESK, should be installed for voltages greater than 250V (L1, L2, L3) between identical terminal points of adjacent modules. Potential bridging is then possible with the XRAFBST bridge system.
2 The current rating for the normally open contact (#14) is 10 A. The current rating for the normally closed contact (#12) is 6 A and can be increased to 10 A by bridging the two #12 contact connections.